Title :
Improving frequency measurements: switching loads
Author :
Donolo, Marcos A. ; Centeno, Virgilio A. ; Liu, Yilu
Author_Institution :
Virginia Polytech. Inst. & State Univ., Blacksburg, VA
Abstract :
Frequency recording units (FRUs), designed to measure power systems´ frequency at low voltage, are affected by the connection of large loads causing sudden phase shifts and magnitude changes in the voltage. These phase shifts introduce spikes in the frequency measured by FRUs. In this paper, we propose an algorithm to detect the phase shifts and to produce an accurate frequency estimation regardless of load changes
Keywords :
frequency measurement; phase measurement; power system measurement; frequency estimation; frequency measurements; frequency recording units; phase shift detection; switching loads; Data mining; Frequency estimation; Frequency measurement; Low voltage; Measurement units; Phase measurement; Phasor measurement units; Power measurement; Power system analysis computing; Power system measurements; Frequency measurement; phasor measurement; phasor measurement unit (PMU);
Journal_Title :
Power Delivery, IEEE Transactions on
DOI :