• DocumentCode
    774959
  • Title

    Improving frequency measurements: switching loads

  • Author

    Donolo, Marcos A. ; Centeno, Virgilio A. ; Liu, Yilu

  • Author_Institution
    Virginia Polytech. Inst. & State Univ., Blacksburg, VA
  • Volume
    21
  • Issue
    4
  • fYear
    2006
  • Firstpage
    1803
  • Lastpage
    1808
  • Abstract
    Frequency recording units (FRUs), designed to measure power systems´ frequency at low voltage, are affected by the connection of large loads causing sudden phase shifts and magnitude changes in the voltage. These phase shifts introduce spikes in the frequency measured by FRUs. In this paper, we propose an algorithm to detect the phase shifts and to produce an accurate frequency estimation regardless of load changes
  • Keywords
    frequency measurement; phase measurement; power system measurement; frequency estimation; frequency measurements; frequency recording units; phase shift detection; switching loads; Data mining; Frequency estimation; Frequency measurement; Low voltage; Measurement units; Phase measurement; Phasor measurement units; Power measurement; Power system analysis computing; Power system measurements; Frequency measurement; phasor measurement; phasor measurement unit (PMU);
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/TPWRD.2006.874564
  • Filename
    1705534