• DocumentCode
    775091
  • Title

    The case for frequency domain PD testing in the context of distribution cable

  • Author

    Boggs, Steven

  • Author_Institution
    Electr. Insulation Res. Center, Connecticut Univ., Storrs, CT, USA
  • Volume
    19
  • Issue
    4
  • fYear
    2003
  • Firstpage
    13
  • Lastpage
    19
  • Abstract
    Frequency domain PD testing offers a rich set of PD characterization tools, the most basic of which are described in the article. PD detection sensitivity under field conditions is one to two orders of magnitude greater than for time domain testing as a result of (i) no need to trigger on the first PD pulse above the broadband noise, and (ii) the filtering effect of the cable between the PD detection site and the terminations. As a result of this greatly increased sensitivity and the rich set of characterization tools, frequency domain PD testing has been developed into a highly sensitive and reliable tool for characterizing the condition of distribution cable during normal operation, the sensitivity and accuracy of which have been confirmed through independent testing.
  • Keywords
    frequency-domain analysis; insulation testing; partial discharge measurement; power cable insulation; power cable testing; sensitivity; trees (electrical); PD characterization tools; PD detection site; PD pulse; broadband noise; distribution cable; frequency domain PD testing; partial discharge testing; sensitivity; time domain testing; water trees; Computer aided software engineering; Dielectrics; Frequency domain analysis; Partial discharges; Power cables; RLC circuits; Resonance; Space vector pulse width modulation; Testing; Voltage;
  • fLanguage
    English
  • Journal_Title
    Electrical Insulation Magazine, IEEE
  • Publisher
    ieee
  • ISSN
    0883-7554
  • Type

    jour

  • DOI
    10.1109/MEI.2003.1226730
  • Filename
    1226730