DocumentCode
775913
Title
Harmonic generation by HVDC schemes involving converters and static VAr compensators
Author
Yacamini, R. ; Resende, J.W.
Author_Institution
Dept. of Eng., Aberdeen Univ., UK
Volume
143
Issue
1
fYear
1996
fDate
1/1/1996 12:00:00 AM
Firstpage
66
Lastpage
74
Abstract
The paper makes use of interactive harmonic analysis (IHA) to examine the harmonic behaviour of an HVDC scheme. The scheme is treated as a complete system including HVDC converters, static VAr compensators, system impedance and harmonic filters. It is shown that the type and performance of the controller can have a significant effect on harmonic behaviour. The paper illustrates, by analytical and computational analysis, the effect of equally pulse spaced (EPS) controllers and voltage zero crossing (VZC) type for both the above power electronic circuits. The EPS has clear advantages for 6 and 12 pulse HVDC converters but has little influence on the behaviour of thyristor controlled reactors. The need to represent the complete systems is highlighted by example
Keywords
HVDC power convertors; filters; harmonic analysis; power system control; power system harmonics; static VAr compensators; voltage control; voltage regulators; 12 pulse HVDC converters; 6 pulse HVDC converters; HVDC converters; HVDC schemes; equally pulse spaced controllers; harmonic filters; harmonic generation; interactive harmonic analysis; power electronic circuits; static VAr compensators; system impedance; thyristor controlled reactors; voltage zero crossing controllers;
fLanguage
English
Journal_Title
Generation, Transmission and Distribution, IEE Proceedings-
Publisher
iet
ISSN
1350-2360
Type
jour
DOI
10.1049/ip-gtd:19960046