DocumentCode
778114
Title
Study on Transmission-Line Arresters for Tower With High Footing Resistance
Author
Hayashi, Tomohiro ; Mizuno, Yukio ; Naito, Katsuhiko
Author_Institution
Power Bus. Group, NGK Insulators Ltd., Nagoya
Volume
23
Issue
4
fYear
2008
Firstpage
2456
Lastpage
2460
Abstract
The countermeasure against lightning faults is one of the most decisive factors in designing a transmission line in a high grounding resistance area. The higher the footing resistance is, the higher the resulting lightning surge voltage borne by the insulator string is. But it is practically not so easy to decrease the tower footing resistance. Lightning arresters for the transmission line have been developed and are already in successful service. However, the application effect of line arresters to the tower of high footing resistance has not been studied yet. This paper describes the results of computer calculation regarding the application effect of transmission-line arresters assuming typical parameters of the 77-kV line in Japan. As a result, the line arresters can effectively prevent the lightning faults in an area of high footing resistance.
Keywords
arresters; earthing; lightning protection; poles and towers; power overhead lines; power transmission protection; Japan; high footing resistance; high grounding resistance area; insulator string; lightning faults; lightning surge voltage; tower; transmission-line arresters; voltage 77 kV; Arresters; lightning; towers; transmission lines;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/TPWRD.2008.917892
Filename
4555696