Abstract :
Test equipment is described which is suitable for AC hipot and partial discharge testing of 5 and 15 kV shielded cables of lengths up to about 600 m. The equipment can be used to test 5 and 15 kV metal-clad switchgear. Ontario Hydro´s experience at two nuclear generating stations using this AC test equipment is presented. The equipment can be used to assure the integrity of cable systems (less than 600 m long) already in service. The reasons for switching to AC testing of cable systems are outlined. Practical experience shows that the partial-discharge test is very effective in identifying installation problems in cables and switchgear. A number of problems are identified with the AC tests that a DC test would have missed
Keywords :
cable testing; partial discharges; power cables; switchgear; switchgear testing; 5 to 15 kV; AC hipot testing; commissioning; generating station cables; nuclear generating stations; partial discharge tests; shielded cables; switchgear; AC generators; Cable insulation; Circuit testing; Partial discharges; Power cables; Power supplies; Switchgear; System testing; Test equipment; Voltage;