• DocumentCode
    778666
  • Title

    Prevention of Reliability Degradation from Recloser–Fuse Miscoordination Due To Distributed Generation

  • Author

    Chaitusaney, Surachai ; Yokoyama, Akihiko

  • Author_Institution
    Dept. of Electr. Eng., Univ. of Tokyo, Tokyo
  • Volume
    23
  • Issue
    4
  • fYear
    2008
  • Firstpage
    2545
  • Lastpage
    2554
  • Abstract
    Distributed generation (DG) may bring about reliability degradation, instead of reliability enhancement, due to recloser-fuse miscoordination. For the prevention of this reliability degradation, this paper proposes a method to find the threshold value of the DG capacity, beyond which recloser-fuse coordination is lost. Mathematical equations for protective devices are used to set up the protection settings and calculate the threshold value. Three reliability indices-SAIFI, SAIDI, and ENS-are evaluated and compared with the study cases in the reliability test system RBTS bus 2. The results show that the proposed method is effective to prevent the deterioration of system reliability. In addition, a simple modification to the protection system is presented as a preliminary solution.
  • Keywords
    electric fuses; electric power generation; power system management; power system reliability; DG capacity; distributed generation; protective devices; recloser fuse coordination; recloser fuse miscoordination; reliability degradation; reliability test system; threshold value; Distributed generation (DG); distribution system; fuse; generation threshold; protection miscoordination; recloser; reliability;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/TPWRD.2007.915899
  • Filename