DocumentCode :
781723
Title :
An investigation into the use of adaptive setting techniques for improved distance back-up protection
Author :
Stedall, B. ; Moore, P. ; Johns, A. ; Goody, J. ; Burt, M.
Author_Institution :
Sch. of Electron. & Electr. Eng., Bath Univ., UK
Volume :
11
Issue :
2
fYear :
1996
fDate :
4/1/1996 12:00:00 AM
Firstpage :
757
Lastpage :
762
Abstract :
Changes in power system operating conditions adversely affect the reach point accuracy of distance relays. This paper discusses adaptation of the settings of distance relays within an integrated digital hierarchical protection system for the optimisation of relay performance. Specific reference is made to adaptation of the zone 3 setting to ensure optimal relay performance over a wide variety of operating conditions. Results illustrating the performance of adaptive methods compared to conventional fixed setting are presented for an application study of the North Wales 400 kV transmission network, UK
Keywords :
adaptive control; hierarchical systems; optimal control; power system control; power system protection; power system relaying; power transmission; relay protection; transmission networks; 400 kV; UK; adaptive setting techniques; distance back-up protection; distance relays; integrated digital hierarchical protection system; power system operating conditions; reach point accuracy; relay performance optimisation; transmission network; zone 3 setting; Adaptive systems; Computerized monitoring; Digital relays; Industrial power systems; Power system modeling; Power system protection; Power system relaying; Power system reliability; Protective relaying; SCADA systems;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/61.489332
Filename :
489332
Link To Document :
بازگشت