• DocumentCode
    781876
  • Title

    Suppression of VFT in 1100 kV GIS by adopting resistor-fitted disconnector

  • Author

    Yamagata, Y. ; Tanaka, K. ; Nishiwaki, S. ; Takahashi, N. ; Kokumai, T. ; Miwa, I. ; Komukai, T. ; Imai, K.

  • Author_Institution
    Tokyo Electr. Power Co. Inc., Japan
  • Volume
    11
  • Issue
    2
  • fYear
    1996
  • fDate
    4/1/1996 12:00:00 AM
  • Firstpage
    872
  • Lastpage
    880
  • Abstract
    With 1000 kV transmission lines planned in Japan, very fast transient (VFT) phenomena will be suppressed by installing a resistor in a disconnector of gas insulated switchgear (GIS). In this paper the VFT overvoltage suppressing effect of the resistor and the duty required of the resistor are clarified. A 1100 kV resistor-fitted disconnector was tested by constructing a charging current interruption test circuit. It has been clarified that the disconnector accepts the required duty. The disconnector tested is used for the field test
  • Keywords
    gas insulated switchgear; overvoltage protection; power system protection; switchgear testing; 1000 kV; 1100 kV; GIS; charging current interruption test circuit; disconnector testing; gas insulated switchgear; overvoltage suppressing effect; resistor; resistor-fitted disconnector; very fast transients suppression; Circuit testing; Electrodes; Gas insulated transmission lines; Gas insulation; Geographic Information Systems; Power system transients; Power transformer insulation; Power transmission lines; Resistors; Switchgear; Switching circuits; Voltage control;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.489346
  • Filename
    489346