Title :
Measurement of lightning surges on test transmission line equipped with arresters struck by natural and triggered lightning
Author :
Matsumoto, Y. ; Sakuma, O. ; Shinjo, K. ; Saiki, M. ; Wakai, T. ; Sakai, T. ; Nagasaka, H. ; Motoyama, Hideki ; Ishii, M.
Author_Institution :
Hokuriku Electr. Power Co., Toyama, Japan
fDate :
4/1/1996 12:00:00 AM
Abstract :
Measurement of lightning surges caused by natural or rocket-triggered lightning strokes has been carried out on a 275 kV test transmission line since 1987. In November 1993, lightning currents at the tower top, the ground wires, the tower legs and the transmission line arresters, along with the voltages across the insulator strings were measured simultaneously four times. One of the four flashes was natural lightning, and its peak value was +132 kA. In this case, the arresters operated, and the insulator voltages where the arresters were equipped were controlled properly. The result of a multi-phase analysis by EMTP agreed well with the measured waveforms
Keywords :
arresters; insulators; lightning protection; poles and towers; power overhead lines; power system measurement; power transmission lines; surges; voltage measurement; 275 kV; EMTP; ground wires; insulator voltages control; lightning currents; lightning surges measurement; multi-phase analysis; natural lightning; rocket triggered lightning; test transmission line; tower legs; transmission line arresters; Arresters; Cable insulation; Leg; Lightning; Poles and towers; Surges; Testing; Transmission line measurements; Voltage; Wires;
Journal_Title :
Power Delivery, IEEE Transactions on