DocumentCode :
784334
Title :
Development of 138 kV transition joint between HPPT cable and extruded cable
Author :
Chu, H. ; Ghafurian, R. ; Maguire, K. ; Parmigiani, B. ; Walker, J.
Author_Institution :
Consolidated Edison Co., New York, NY, USA
Volume :
7
Issue :
4
fYear :
1992
fDate :
10/1/1992 12:00:00 AM
Firstpage :
1718
Lastpage :
1723
Abstract :
The authors describe the successful development of a 138 kV transition joint between high-pressure dielectric-fluid-filled cable with paper insulation and cable with extruded insulation, such as cross-linked polyethylene or ethylene propylene rubber. Such a joint must have adequate electrical and mechanical properties and contain the high-pressure dielectric fluid normally at 1400 kPa. For evaluation of the transition joint, the IEEE standard 404-1986 for laminar-to-laminar cable joints and extruded-to-extruded cable joints was considered, along with many of the specified types of tests included, such as high-voltage AC and DC, hot impulse to BIL, cyclic aging, and corona. The test results are reported
Keywords :
cable insulation; cable jointing; high-voltage techniques; organic insulating materials; paper; polymers; power cables; testing; 138 kV; 1400 kPa; HVAC testing; HVDC testing; IEEE standard 404-1986; corona testing; cross-linked polyethylene; cyclic aging; electrical properties; ethylene propylene rubber; extruded insulation; extruded-to-extruded cable joints; high-pressure dielectric-fluid-filled cable; hot impulse testing; laminar-to-laminar cable joints; mechanical properties; paper insulation; transition joint; Cable insulation; Cables; Circuit testing; Conducting materials; Conductors; Copper; Dielectrics and electrical insulation; Paramagnetic resonance; Solids; Voltage;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/61.156971
Filename :
156971
Link To Document :
بازگشت