• DocumentCode
    784446
  • Title

    New fault locating system for air-insulated substations using optical current detector

  • Author

    Yoshida, Y. ; Kawazoe, S. ; Ibuki, K. ; Yamada, K. ; Ochi, N.

  • Author_Institution
    Kansai Electric Power Co. Inc., Osaka, Japan
  • Volume
    7
  • Issue
    4
  • fYear
    1992
  • fDate
    10/1/1992 12:00:00 AM
  • Firstpage
    1805
  • Lastpage
    1812
  • Abstract
    The authors present the basic philosophy, construction, design features, and test results of a new fault locating system. This fault locating system helps to shorten the time required for restoration of service after the occurrence of a busbar fault in an air-insulated distribution substation. Recent optical and electronic technologies allow the design of a highly accurate and compact fault locating system which consists of optical current detectors using the Faraday effect and a fault locating processor using a digital data processing technique. The fault location is carried out by discriminating between the directions of zero-sequence currents. Through various tests and field operations, it has been confirmed that the system has sufficient performance for practical applications
  • Keywords
    digital instrumentation; electric current measurement; fault location; fibre optic sensors; signal processing equipment; substations; Faraday effect; air-insulated substations; busbar fault; digital data processing; fault locating system; optical current detectors; service restoration; zero-sequence currents; Electrical fault detection; Fault detection; Fault location; Optical detectors; Optical sensors; Power system reliability; Power system restoration; Substations; Switches; System testing;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.156982
  • Filename
    156982