• DocumentCode
    784645
  • Title

    Development of an advanced transmission line fault location system. II. Algorithm development and simulation

  • Author

    Lawrence, David J. ; Cabeza, Luis Z. ; Hochberg, Lawrence T.

  • Author_Institution
    Power Technologies Inc., Schenectady, NY, USA
  • Volume
    7
  • Issue
    4
  • fYear
    1992
  • fDate
    10/1/1992 12:00:00 AM
  • Firstpage
    1972
  • Lastpage
    1983
  • Abstract
    For pt.I see ibid., vol.7, no.4, p.1963-71 (1992). The authors describe the solution techniques, system modeling considerations, and simulation studies performed as a part of the development of an advanced transmission line fault location system intended for use on the New York Power Authority´s system. The Power Authority´s Moses-Adirondack 230 kV lines were selected as a testbed for the study. A reduced model of the transmission system around the Moses-Adirondack lines was developed, and a number of electromagnetic transients program (EMTP) cases were run to establish simulated voltage and current information as fed to the fault location system. Sensitivity studies were performed to investigate the impact of various system models, hardware features, and system conditions on fault location accuracy
  • Keywords
    digital simulation; fault location; power system analysis computing; power transmission lines; 230 kV; EMTP; Moses-Adirondack 230 kV lines; New York Power Authority; electromagnetic transients program; sensitivity studies; simulation studies; system modeling; transmission line fault location system; Circuit faults; EMTP; Fault location; Monitoring; Power system modeling; Power transmission lines; Substations; Transducers; Transmission lines; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.157001
  • Filename
    157001