DocumentCode
784683
Title
Harmonic power flow analysis for the measurement of the electric power quality
Author
Cristaldi, Loredana ; Ferrero, Alessandro
Author_Institution
Dipartimento di Elettrotecnica, Politecnico di Milano, Italy
Volume
44
Issue
3
fYear
1995
fDate
6/1/1995 12:00:00 AM
Firstpage
683
Lastpage
685
Abstract
The number and power of loads that pollute, from an electric point of view, the electric network are constantly increasing. Their connection to the electric network causes a significant distortion in the line current and, when their overall power is no longer negligible with respect to the network power, also some distortion in the line voltage, thus deteriorating the electric supply quality. The paper proposes a method, based on the evaluation of the harmonic powers, to identify whether the source producing harmonic distortion in the line currents and voltages of a three-phase system is a polluting load connected after the metering section or is the distortion of the line voltages. Some parameters are also defined in order to quantify the effects of the polluting load on the power quality. A Virtual Instrument is also described, realized to implement the proposed method and to verify it experimentally. The instrument accuracy is discussed
Keywords
computerised instrumentation; harmonic distortion; load flow; load management; power system harmonics; power system measurement; virtual machines; Virtual Instrument; accuracy; distortion; electric power quality; harmonic distortion; harmonic power flow analysis; harmonic powers; line current; line voltages; polluting load; three-phase system; Distortion measurement; Electric variables measurement; Fluid flow measurement; Harmonic distortion; Instruments; Load flow analysis; Pollution; Power measurement; Power system harmonics; Voltage;
fLanguage
English
Journal_Title
Instrumentation and Measurement, IEEE Transactions on
Publisher
ieee
ISSN
0018-9456
Type
jour
DOI
10.1109/19.387308