Title
Niew Apparatus for Detecting Transformer Faults
Author
Tsukioka, H. ; Sugawara, K. ; Mori, E. ; Yamaguchi, H.
Author_Institution
Hitachi Research Laboratory Hitachi, Ltd, Hitachi City, Japan
Issue
2
fYear
1986
fDate
4/1/1986 12:00:00 AM
Firstpage
221
Lastpage
229
Abstract
A diagnostic apparatus for detecting gases dissolved in transformer oil is described, in which a tetrafluoroethylene-perfluoroalkylvinylether copolymer membrane is used to separate H2 CO, CH4, C2H2, C2H4, and C2H6 from the oil. These gases are detected with a new gas detector, which consists of a catalytic gas sensor and a gas chromatograph using air as the carrier gas. Using the gas concentration, the apparatus automatically determines whether a transformer is operating normally or not and, in the latter case, what kind of fault may have occurred. By the above diagnostic apparatus, a transformer could be diagnosed simply and inexpensively. This apparatus should prove useful for identifying what kind of fault may have occurred.
Keywords
Biomembranes; Fault detection; Gas detectors; Gas insulation; Gases; Hydrogen; Oil insulation; Petroleum; Polymers; Power transformer insulation;