• DocumentCode
    786520
  • Title

    Hybrid three phase load flow

  • Author

    Chen, B.-K. ; Chen, M.-S. ; Shoults, R.R. ; Liang, C.-C.

  • Author_Institution
    Dept. of Electr. Eng., Tatung Inst. of Technol., Taipei, Taiwan
  • Volume
    137
  • Issue
    3
  • fYear
    1990
  • fDate
    5/1/1990 12:00:00 AM
  • Firstpage
    177
  • Lastpage
    185
  • Abstract
    The development of a unique three phase load flow algorithm is presented which employs a hybrid (implicit Z-BUS and Y-BUS Gauss) iterative technique without making any nonpractical assumptions about the generators. The main applications of this three phase load flow program will be to find optimum line configuration when a utility wants to construct a new transmission line, to find the optimum transposition positions and line arrangements through a system, and for estimation of generator current unbalance during normal operation
  • Keywords
    iterative methods; load flow; Y-BUS Gauss method; Z-BUS Gauss method; generator current unbalance; iterative technique; optimum line configuration; three phase load flow; transmission line;
  • fLanguage
    English
  • Journal_Title
    Generation, Transmission and Distribution, IEE Proceedings C
  • Publisher
    iet
  • ISSN
    0143-7046
  • Type

    jour

  • Filename
    48967