DocumentCode :
789964
Title :
Arc modelling in SF6 circuit breakers
Author :
Vérité, J.C. ; Boucher, T. ; Comte, A. ; Delalondre, C. ; Robin-Jouan, P. ; Serres, E. ; Texier, V. ; Barrault, M. ; Chevrier, P. ; Fievet, C.
Author_Institution :
Direction des Etudes et Recherches, Electr. de France, Clamart, France
Volume :
142
Issue :
3
fYear :
1995
fDate :
5/1/1995 12:00:00 AM
Firstpage :
189
Lastpage :
196
Abstract :
The problem of the physical modelling of SF6 arcs in circuit breakers is considered. The authors present results concerning the simulation of two model breakers (one of a two pressure breaker and the other of a rotary arc breaker) using numerical programs involving different physical models and assumptions. It is shown that it is necessary to take compressibility into account and also the complete radiation process including absorption in cold regions. The authors discuss the assumptions and the importance of phenomena like turbulence and Lorentz forces and compare some available experimental data
Keywords :
SF6 insulation; circuit-breaking arcs; digital simulation; electrical engineering computing; gas blast circuit breakers; turbulence; Lorentz forces; SF6; SF6 arcs; SF6 circuit breakers; arc modelling; compressibility; numerical programs; physical modelling; plasma torches; pressure breaker; radiation process; rotary arc breaker; simulation; turbulence; two model breakers;
fLanguage :
English
Journal_Title :
Science, Measurement and Technology, IEE Proceedings -
Publisher :
iet
ISSN :
1350-2344
Type :
jour
DOI :
10.1049/ip-smt:19951781
Filename :
388324
Link To Document :