DocumentCode
792193
Title
Direct Powering of the 200-GeV Synchrotron Magnets from the Utility System
Author
Cassel, R.L. ; Van Ness, J.E.
Author_Institution
National Accelerator Laboratory Batavia, Illinois
Volume
16
Issue
3
fYear
1969
fDate
6/1/1969 12:00:00 AM
Firstpage
672
Lastpage
676
Abstract
The main magnet system of the 200-GeV synchrotron of the National Accelerator Laboratory will be directly powered from the utilities without the use of local energy storage. The utility connections, power supply arrangement, and control philosophy have been adjusted to accommodate the difficulties generated by the direct connection. A system analysis was performed to ascertain if any stability or utility-line disturbance would be generated by the connection. Sophisticated controls will be utilized to minimize the effect of utility-line variations on the accelerator regulation. The result is a total system with no apparent degradation in the performance of the accelerator or the utility system.
Keywords
Accelerator magnets; Degradation; Energy storage; Laboratories; Magnetic analysis; Performance analysis; Power generation; Power supplies; Stability analysis; Synchrotrons;
fLanguage
English
Journal_Title
Nuclear Science, IEEE Transactions on
Publisher
ieee
ISSN
0018-9499
Type
jour
DOI
10.1109/TNS.1969.4325330
Filename
4325330
Link To Document