DocumentCode
792262
Title
Voltage stability limit of electric power systems with Generator reactive power constraints considered
Author
Kataoka, Yoshihiko ; Shinoda, Yukio
Author_Institution
Tokyo Electr. Power Co. Inc, Yokohama, Japan
Volume
20
Issue
2
fYear
2005
fDate
5/1/2005 12:00:00 AM
Firstpage
951
Lastpage
962
Abstract
This paper investigates the smoothness of the transfer limit surface, or the loadability surface, of power systems. The reactive power output constraints of generators are taken into consideration. A new methodology employed for the investigation is based on characterizing each maximum loading point by the state of the generators (PV or PQ). Then the transfer limit surface is investigated through careful observation of nose curves. In those special cases with only one constraint, the transfer limit surface is smooth. However, in the more general case of multiple constraints, the transfer limit surface is nonsmooth. These properties have been confirmed in a numerical example using a system with two constraints and three load parameters.
Keywords
electric generators; power system stability; reactive power; electric power system; loadability surface; reactive power constraint; transfer limit surface; voltage stability limit; Bifurcation; Character generation; Nose; Power generation; Power system modeling; Power system reliability; Power system stability; Reactive power; Steady-state; Voltage; Bifurcation set; electric power system; generator reactive power limits; inequality constraints; static model; transfer limit surface; voltage stability;
fLanguage
English
Journal_Title
Power Systems, IEEE Transactions on
Publisher
ieee
ISSN
0885-8950
Type
jour
DOI
10.1109/TPWRS.2005.846080
Filename