Abstract
A new technique for analyzing partial discharge (PD) signals based on ultra-high frequency (UHF) measurements is presented, using results from site tests. Signals from simultaneously active discharge sources can be mapped according to their point of origin in a manner that will simplify the interpretation of phase-resolved discharge patterns. The scheme has the potential to allow automated location and tracking of multiple discharge sources in power transformers and other metal-clad high-voltage plants.
Keywords
UHF measurement; insulation testing; partial discharge measurement; power transformer insulation; power transformer testing; PD signals analysis; UHF partial discharge detection; metal-clad high-voltage plants; multiple discharge sources; phase-resolved discharge patterns interpretation; power transformer insulation testing; simultaneously active discharge sources; ultra-high frequency measurements; Fault location; Frequency; Geographic Information Systems; Partial discharges; Power transformers; Pulse measurements; Pulse transformers; Sensor phenomena and characterization; Testing; UHF measurements;