DocumentCode :
795434
Title :
Digital location of partial discharges in HV cables
Author :
Borsi, H.
Author_Institution :
Inst. for High Voltage Eng., Hannover Univ., Germany
Volume :
27
Issue :
1
fYear :
1992
fDate :
2/1/1992 12:00:00 AM
Firstpage :
28
Lastpage :
36
Abstract :
This paper deals with a new digital system for locating partial discharges (PDs) in high voltage (HV) cables under noisy conditions. After an introduction to different PD location methods and their limits, the possibility of PD location through the pulse separation method is introduced. Digital filtering performed with predictor filters is described. Extensive investigations are carried out to determine the effectiveness of these filters, as well as their limitations, in their use for PD and noise separation. The results concerning the application of filtering on PD and noise signals measured on an HV cable under noisy conditions are presented
Keywords :
cable testing; charge measurement; digital filters; fault location; partial discharges; power cables; HV cables; digital filtering; digital location; digital system; noise separation; noisy conditions; partial discharges; predictor filters; pulse separation method; Attenuation; Cable insulation; Digital filters; Digital systems; Fault location; Filtering; Manufacturing; Partial discharges; Pulse measurements; Voltage;
fLanguage :
English
Journal_Title :
Electrical Insulation, IEEE Transactions on
Publisher :
ieee
ISSN :
0018-9367
Type :
jour
DOI :
10.1109/14.123438
Filename :
123438
Link To Document :
بازگشت