• DocumentCode
    797069
  • Title

    Reliability Considerations in Systems Applications of Uninterruptible Power Supplies

  • Author

    Heising, Charles R. ; Johnston, James F., Jr.

  • Author_Institution
    Power Transmission Division, General Electric Company, Philadelphia, Pa. 19142.
  • Issue
    2
  • fYear
    1972
  • fDate
    3/1/1972 12:00:00 AM
  • Firstpage
    104
  • Lastpage
    107
  • Abstract
    A redundant static inverter is applied as an uninterruptible power supply (UPS). A reliability analysis is presented showing that the introduction of a static bypass transfer switch brings about a reliability improvement of 8.5 to 1 in the mean time between failure (MTBF). This gives MTBF greater than 600 000 h. The static bypass transfer switch provides a synchronized automatic transfer in less than 1 ms from the UPS to the normal ac input power source upon a failure of the UPS.
  • Keywords
    Batteries; Failure analysis; Interrupters; Inverters; Oscillators; Power supplies; Power system reliability; Rectifiers; Switches; Uninterruptible power systems;
  • fLanguage
    English
  • Journal_Title
    Industry Applications, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0093-9994
  • Type

    jour

  • DOI
    10.1109/TIA.1972.349795
  • Filename
    4158212