DocumentCode
797069
Title
Reliability Considerations in Systems Applications of Uninterruptible Power Supplies
Author
Heising, Charles R. ; Johnston, James F., Jr.
Author_Institution
Power Transmission Division, General Electric Company, Philadelphia, Pa. 19142.
Issue
2
fYear
1972
fDate
3/1/1972 12:00:00 AM
Firstpage
104
Lastpage
107
Abstract
A redundant static inverter is applied as an uninterruptible power supply (UPS). A reliability analysis is presented showing that the introduction of a static bypass transfer switch brings about a reliability improvement of 8.5 to 1 in the mean time between failure (MTBF). This gives MTBF greater than 600 000 h. The static bypass transfer switch provides a synchronized automatic transfer in less than 1 ms from the UPS to the normal ac input power source upon a failure of the UPS.
Keywords
Batteries; Failure analysis; Interrupters; Inverters; Oscillators; Power supplies; Power system reliability; Rectifiers; Switches; Uninterruptible power systems;