DocumentCode :
797116
Title :
Experimental results of a supplementary technique for auto-reclosing EHV/UHV transmission lines
Author :
Eissa, Moustafa Mohammed ; Malik, O.P.
Author_Institution :
Dept. of Electr. Eng., Helwan Univ., Cairo, Egypt
Volume :
17
Issue :
3
fYear :
2002
fDate :
7/1/2002 12:00:00 AM
Firstpage :
702
Lastpage :
707
Abstract :
A technique to discriminate between the line charging inrush current and the current resulting on closing or auto-reclosing a faulted EHV/UHV transmission line has been implemented on a 32-b digital signal processor (DSP) board. The technique is based on the voltage signals before switching and the current signals. This technique is proposed to be a supplement to the main protection schemes for both single-circuit and double-circuit lines. The scheme is tested on a physical model of a transmission system with a source at each end. Laboratory tests show that the proposed technique is effective for three-pole and single-pole reclosing on a faulted or healthy line.
Keywords :
power transmission control; power transmission faults; power transmission lines; power transmission protection; 32 bit; EHV/UHV transmission lines auto-reclosure technique; double-circuit lines protection; faulted EHV/UHV transmission line; line charging inrush current; power system protection automation; single-circuit lines protection; single-pole reclosing; switching; three-pole reclosing; Circuit faults; Fault currents; Laboratories; Protection; Protective relaying; Relays; Surges; Testing; Transmission lines; Voltage;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/TPWRD.2002.1022790
Filename :
1022790
Link To Document :
بازگشت