• DocumentCode
    797116
  • Title

    Experimental results of a supplementary technique for auto-reclosing EHV/UHV transmission lines

  • Author

    Eissa, Moustafa Mohammed ; Malik, O.P.

  • Author_Institution
    Dept. of Electr. Eng., Helwan Univ., Cairo, Egypt
  • Volume
    17
  • Issue
    3
  • fYear
    2002
  • fDate
    7/1/2002 12:00:00 AM
  • Firstpage
    702
  • Lastpage
    707
  • Abstract
    A technique to discriminate between the line charging inrush current and the current resulting on closing or auto-reclosing a faulted EHV/UHV transmission line has been implemented on a 32-b digital signal processor (DSP) board. The technique is based on the voltage signals before switching and the current signals. This technique is proposed to be a supplement to the main protection schemes for both single-circuit and double-circuit lines. The scheme is tested on a physical model of a transmission system with a source at each end. Laboratory tests show that the proposed technique is effective for three-pole and single-pole reclosing on a faulted or healthy line.
  • Keywords
    power transmission control; power transmission faults; power transmission lines; power transmission protection; 32 bit; EHV/UHV transmission lines auto-reclosure technique; double-circuit lines protection; faulted EHV/UHV transmission line; line charging inrush current; power system protection automation; single-circuit lines protection; single-pole reclosing; switching; three-pole reclosing; Circuit faults; Fault currents; Laboratories; Protection; Protective relaying; Relays; Surges; Testing; Transmission lines; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/TPWRD.2002.1022790
  • Filename