DocumentCode
797116
Title
Experimental results of a supplementary technique for auto-reclosing EHV/UHV transmission lines
Author
Eissa, Moustafa Mohammed ; Malik, O.P.
Author_Institution
Dept. of Electr. Eng., Helwan Univ., Cairo, Egypt
Volume
17
Issue
3
fYear
2002
fDate
7/1/2002 12:00:00 AM
Firstpage
702
Lastpage
707
Abstract
A technique to discriminate between the line charging inrush current and the current resulting on closing or auto-reclosing a faulted EHV/UHV transmission line has been implemented on a 32-b digital signal processor (DSP) board. The technique is based on the voltage signals before switching and the current signals. This technique is proposed to be a supplement to the main protection schemes for both single-circuit and double-circuit lines. The scheme is tested on a physical model of a transmission system with a source at each end. Laboratory tests show that the proposed technique is effective for three-pole and single-pole reclosing on a faulted or healthy line.
Keywords
power transmission control; power transmission faults; power transmission lines; power transmission protection; 32 bit; EHV/UHV transmission lines auto-reclosure technique; double-circuit lines protection; faulted EHV/UHV transmission line; line charging inrush current; power system protection automation; single-circuit lines protection; single-pole reclosing; switching; three-pole reclosing; Circuit faults; Fault currents; Laboratories; Protection; Protective relaying; Relays; Surges; Testing; Transmission lines; Voltage;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/TPWRD.2002.1022790
Filename
1022790
Link To Document