Title :
A New Noncommunication-Based Protection Scheme for Three-Terminal Transmission Lines Employing Mathematical Morphology-Based Filters
Author :
Khodadadi, M. ; Shahrtash, S.M.
Author_Institution :
Iran Univ. of Sci. & Technol. (IUST), Tehran, Iran
Abstract :
In this paper, a new noncommunication-based scheme is presented for the protection of three-terminal transmission lines. Using this scheme, simultaneous operation of circuit breakers (CBs) at all terminals is provided for all internal faults. This scheme can discriminate between external and internal faults based on initiated transients by faults, considering the high-stop filtering property of busbars through modeling their stray capacitances and employing a newly defined mathematical morphology (MM) filter to analyze the captured transients. Moreover, the transients generated by lightning or switching are identified and prohibited to enter the algorithm. The presented scheme has been applied on one of three-terminal lines in Iran´s Transmission Grid. The effects of fault resistance, fault inception angle, (internal) fault location, and fault type on the performance of the proposed scheme are evaluated, where the high dependability, accuracy, and speed are verified.
Keywords :
busbars; circuit breakers; fault location; mathematical morphology; power filters; power grids; power transmission lines; power transmission protection; CB; Iran transmission grid; MM filter; busbars; circuit breakers; external faults; fault inception angle; fault location; fault resistance; high-stop filtering property; internal faults; mathematical morphology-based filters; noncommunication-based protection scheme; stray capacitances; three-terminal transmission lines; Circuit faults; Lightning; Power transmission lines; Resistance; Switches; Transient analysis; Mathematical morphology (MM); noncommunication; protection; three-terminal transmission line; transient based;
Journal_Title :
Power Delivery, IEEE Transactions on
DOI :
10.1109/TPWRD.2012.2224890