DocumentCode :
811343
Title :
Breakdown voltage and time-to-breakdown as influenced by the steepness of the applied positive impulse
Author :
Abdel-Salam, Mazen ; Turky, Abd E H A
Author_Institution :
Assiut Univ., Egypt
Volume :
24
Issue :
6
fYear :
1988
Firstpage :
1031
Lastpage :
1037
Abstract :
The volume-time criterion is discussed, and a modification is proposed with the aim of predicting breakdown voltages in SF/sub 6/ under positive impulse stresses without introducing an empiricism in the analysis. The electrons initiating the breakdown are those produced by cosmic rays that penetrate to the gas volume. The results obtained, including the breakdown voltage and the time-to-breakdown, as influenced by the steepness of the applied impulse, are discussed and compared with those measured experimentally.<>
Keywords :
electric breakdown of gases; gaseous insulation; sulphur compounds; SF/sub 6/; applied positive impulse steepness; breakdown voltages; time-to-breakdown; volume-time criterion; Avalanche breakdown; Breakdown voltage; Cosmic rays; Electric breakdown; Electrodes; Electrons; Industry Applications Society; Ionization; Probability; Sulfur hexafluoride;
fLanguage :
English
Journal_Title :
Industry Applications, IEEE Transactions on
Publisher :
ieee
ISSN :
0093-9994
Type :
jour
DOI :
10.1109/28.17475
Filename :
17475
Link To Document :
بازگشت