DocumentCode
812047
Title
FEM analysis of 3-D transformer leakage field and eddy current loss in the windings
Author
Guangzheng, Ni ; Xiaoming, Xu ; Weiying, Cheng ; Gangru, Li ; Baidun, Jian ; Zhenghu, Fang ; Xianghua, Li ; Jitai, Xu
Author_Institution
Dept. of Electr. Eng., Zhejiang Univ., Hangzhou, China
Volume
28
Issue
2
fYear
1992
fDate
3/1/1992 12:00:00 AM
Firstpage
1382
Lastpage
1385
Abstract
The authors present a method which resolves the three-dimensional eddy current field into a 3-D time harmonic field external to the windings and n axisymmetric eddy current fields near the coils as an approximation for engineering applications. Because the isoparametric FEM (finite element method) with 3-D vector potential, is used in the time harmonic field analysis whereas, in the n axisymmetric eddy current field analysis, B-spline FEM is used, the method presented can give a solution with an accuracy quite acceptable for engineering purposes. The distributions of leakage fields, eddy current losses, and heat source in the windings obtained are compared with the test results
Keywords
eddy current losses; finite element analysis; magnetic leakage; power engineering computing; power transformers; transformer windings; 3-D time harmonic field; 3-D transformer leakage field; 3-D vector potential; B-spline FEM; FEM analysis; eddy current loss; heat source; power transformers; three-dimensional eddy current field; windings; Coils; Eddy current testing; Eddy currents; Harmonic analysis; Magnetic analysis; Matrices; Power engineering and energy; Reliability engineering; Spline; Temperature;
fLanguage
English
Journal_Title
Magnetics, IEEE Transactions on
Publisher
ieee
ISSN
0018-9464
Type
jour
DOI
10.1109/20.123950
Filename
123950
Link To Document