• DocumentCode
    812047
  • Title

    FEM analysis of 3-D transformer leakage field and eddy current loss in the windings

  • Author

    Guangzheng, Ni ; Xiaoming, Xu ; Weiying, Cheng ; Gangru, Li ; Baidun, Jian ; Zhenghu, Fang ; Xianghua, Li ; Jitai, Xu

  • Author_Institution
    Dept. of Electr. Eng., Zhejiang Univ., Hangzhou, China
  • Volume
    28
  • Issue
    2
  • fYear
    1992
  • fDate
    3/1/1992 12:00:00 AM
  • Firstpage
    1382
  • Lastpage
    1385
  • Abstract
    The authors present a method which resolves the three-dimensional eddy current field into a 3-D time harmonic field external to the windings and n axisymmetric eddy current fields near the coils as an approximation for engineering applications. Because the isoparametric FEM (finite element method) with 3-D vector potential, is used in the time harmonic field analysis whereas, in the n axisymmetric eddy current field analysis, B-spline FEM is used, the method presented can give a solution with an accuracy quite acceptable for engineering purposes. The distributions of leakage fields, eddy current losses, and heat source in the windings obtained are compared with the test results
  • Keywords
    eddy current losses; finite element analysis; magnetic leakage; power engineering computing; power transformers; transformer windings; 3-D time harmonic field; 3-D transformer leakage field; 3-D vector potential; B-spline FEM; FEM analysis; eddy current loss; heat source; power transformers; three-dimensional eddy current field; windings; Coils; Eddy current testing; Eddy currents; Harmonic analysis; Magnetic analysis; Matrices; Power engineering and energy; Reliability engineering; Spline; Temperature;
  • fLanguage
    English
  • Journal_Title
    Magnetics, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9464
  • Type

    jour

  • DOI
    10.1109/20.123950
  • Filename
    123950