DocumentCode
812623
Title
Temperature rise tests on a forced-oil-air cooled (FOA) (OFAF) core-form transformer, including loading beyond nameplate
Author
Thaden, M.V. ; Mehta, S.P. ; Tuli, S.C. ; Grubb, R.L.
Author_Institution
Potomac Electr. Power Co., Washington, DC, USA
Volume
10
Issue
2
fYear
1995
fDate
4/1/1995 12:00:00 AM
Firstpage
913
Lastpage
923
Abstract
Results of temperature rise tests performed in accordance with PC57.119/Draft 12, Recommended Procedures for Performing Temperature Rise Tests on Oil-Immersed Power Transformers at Loads Beyond Nameplate Ratings, are presented. Tested data is compared with calculated values using IEEE and IEC loading guide equations and exponential power constants are determined and are compared with those given in the loading guide. Discussion is offered that may be useful in future drafts of and to the users of the proposed test procedure
Keywords
IEEE standards; cooling; insulation testing; power transformer insulation; power transformer testing; temperature measurement; transformer oil; IEC loading guide equations; IEEE loading guide equations; Oil-Immersed Power Transformers; PC57.119/Draft 12; core-form transformer; exponential power constants; forced-oil-air cooled; heat run test; hot spot temperature; loading beyond nameplate; temperature rise tests; Equations; Oil insulation; Optical fiber sensors; Performance evaluation; Petroleum; Power transformers; Temperature measurement; Temperature sensors; Testing; Transformer cores;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/61.400838
Filename
400838
Link To Document