• DocumentCode
    812827
  • Title

    Electromagnetic interference with electronic apparatus by switching surges in GIS-cable system

  • Author

    Nishiwaki, S. ; Nojima, K. ; Tatara, S. ; Kosakada, M. ; Tanabe, N. ; Yanabu, S.

  • Author_Institution
    Toshiba Corp., Kawasaki, Japan
  • Volume
    10
  • Issue
    2
  • fYear
    1995
  • fDate
    4/1/1995 12:00:00 AM
  • Firstpage
    739
  • Lastpage
    746
  • Abstract
    Thyristor malignitions and protector relay failures caused by gas circuit breakers closing in the gas insulated switchgear (GIS) of a power cable system could not be controlled by reducing the ground impedance or adding surge absorbing capacitors. As a result, a study was carried out on this problem with a 66 kV mock-up apparatus installed in a factory. It was found that malignitions and failures such as those mentioned above could be controlled by preventing 10 MHz ultra high-frequency surges emitted by the GIS from leaking out into the grounding system
  • Keywords
    circuit breakers; distribution networks; earthing; electromagnetic interference; industrial power systems; power cables; power system protection; power system relaying; power system transients; surge protection; switchgear testing; test facilities; thyristor applications; 10 MHz; 66 kV; electromagnetic interference; factory; gas insulated switchgear; gas-blast circuit breakers; grounding system; industry; power cable system; power systems; protector relay failures; switching surges; thyristor malignitions; ultra high-frequency surges; Circuit breakers; Control systems; Electromagnetic interference; Gas insulation; Geographic Information Systems; Power system protection; Power system relaying; Protective relaying; Surge protection; Thyristors;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.400857
  • Filename
    400857