DocumentCode :
813542
Title :
Impedance of multigrounded neutrals on rural distribution systems
Author :
Rajotte, Yves ; Fortin, Jacques ; Raymond, Georges
Author_Institution :
Hydro-Quebec, Canada
Volume :
10
Issue :
3
fYear :
1995
fDate :
7/1/1995 12:00:00 AM
Firstpage :
1453
Lastpage :
1459
Abstract :
Hydro-Quebec has conducted field tests to study the impedance of multigrounded neutrals on rural distribution systems. Phase-to-neutral faults were staged at different locations along a 25 kV line and the field test results are reported. A simplified computer model implemented on EMTP gives results very close to those yielded by field tests. The main conclusion is that customers´ grounding systems determine the impedance of multigrounded neutrals. Test results also show that the current is shared more or less equally between the neutral conductor and the sheaths of CATV and telephone cables. Overvoltages on phase conductors during phase-to-neutral faults were also measured and results are presented
Keywords :
digital simulation; distribution networks; earthing; electric impedance measurement; overvoltage; overvoltage protection; power system analysis computing; power system measurement; power system protection; software packages; voltage measurement; 25 kV; EMTP; computer model; field test; impedance measurements; multigrounded neutrals; overvoltages; phase conductors; phase-to-neutral faults; power systems; rural distribution systems; Circuit faults; Communication cables; Conductors; Grounding; Impedance; Phase measurement; Surges; Telephony; Testing; Voltage;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/61.400929
Filename :
400929
Link To Document :
بازگشت