DocumentCode
813725
Title
Infeasible harmonic power flow study solutions
Author
Sainz, L. ; Pedra, J.
Author_Institution
Dept. of Electr. Eng., Univ. Politecnica de Catalunya, Barcelona, Spain
Volume
10
Issue
3
fYear
1995
fDate
7/1/1995 12:00:00 AM
Firstpage
1621
Lastpage
1627
Abstract
Multiple harmonic load flow study solutions are mathematically possible but not physically real. The Newton method can provide these false solutions when an ill-conditioned power system is studied. This problem is more usual in the presence of harmonics. This paper analytically studies a kind of raise solution in networks with AC/DC power converters. These false solutions are easily detected because they present a negative firing angle of the power converter. A simple example is studied where the Newton method gives a false solution
Keywords
AC-DC power convertors; Newton method; load flow; power system harmonics; AC/DC power converters; Newton method; ill-conditioned power system; infeasible harmonic load flow; multiple harmonic load flow; negative firing angle; Bibliographies; DC-DC power converters; Load flow; Load flow analysis; Newton method; Nonlinear equations; Power system analysis computing; Power system harmonics; Power system modeling; Voltage;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/61.400948