On the assessment of harmonic pollution [of power systems]
Author :
Emanuel, Alexander Eigeles
Author_Institution :
Worcester Polytech. Inst., MA, USA
Volume :
10
Issue :
3
fYear :
1995
fDate :
7/1/1995 12:00:00 AM
Firstpage :
1693
Lastpage :
1698
Abstract :
This paper analyses the interactions between the incremental changes of current harmonic phasors injected by a power system NL (nonlinear load) and the resulting variations of harmonic voltages and powers. It proves that it is not always possible, following simple measurements of individual harmonic powers, to decide if a certain harmonic current is harmful or useful. It is suggested that the NL “distortion” be evaluated with the help of a quantity called non60 Hz (nonfundamental) apparent power
Keywords :
harmonic distortion; load (electric); matrix algebra; power supply quality; power system harmonics; 60 Hz; current harmonic phasors; distortion; harmonic current; harmonic pollution assessment; harmonic power; harmonic voltage; measurements; nonfundamental apparent power; nonlinear load; power systems; Current measurement; Equations; Harmonic distortion; Monitoring; Pollution measurement; Power engineering and energy; Power system economics; Power system harmonics; Vectors; Voltage;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :