DocumentCode
815443
Title
Insulation Problems in Medium-Voltage Stator Coils Under Fast Repetitive Voltage Pulses
Author
Haq, Saeed Ul ; Jayaram, Shesha H. ; Cherney, Edward A.
Author_Institution
Dept. of Electr. & Comput. Eng., Univ. of Waterloo, Toronto, ON
Volume
44
Issue
4
fYear
2008
Firstpage
1004
Lastpage
1012
Abstract
In this paper, the degradation processes in stator-bar groundwall insulation that is subjected to steep-front voltage pulses, at different temperatures, are studied. The test conditions include pulse voltage amplitudes up to 6kVp and pulse switching frequencies up to 3 kHz in ambient temperatures of 23degC , 120degC , and 155degC . During the aging process, the surface temperature is monitored with an infrared camera to determine the regions with highest temperatures and the partial discharge (PD) activity. The visual examination of failed bars confirmed that the groundwall insulation in these regions is degraded.
Keywords
ageing; induction motors; insulation testing; machine insulation; machine testing; monitoring; partial discharges; stators; aging process; degradation process; fast repetitive steep-front voltage pulse; groundwall insulation test; induction motor; infrared camera; medium-voltage stator coils; partial discharge; surface temperature monitoring; temperature 120 C; temperature 155 C; temperature 23 C; Aging; Coils; Degradation; Insulation; Medium voltage; Partial discharges; Stators; Switching frequency; Temperature; Testing; Adjustable-speed drives; converters; dielectric heating; groundwall insulation; induction motor; partial discharge (PD); pulse voltage; solid-state switches;
fLanguage
English
Journal_Title
Industry Applications, IEEE Transactions on
Publisher
ieee
ISSN
0093-9994
Type
jour
DOI
10.1109/TIA.2008.926305
Filename
4578787