DocumentCode :
817285
Title :
New approach to power line protection based upon the detection of fault induced high frequency signals
Author :
Johns, A.T. ; Agrawal, P.
Author_Institution :
Power & Energy Syst. Res. Centre, City Univ., London, UK
Volume :
137
Issue :
4
fYear :
1990
fDate :
7/1/1990 12:00:00 AM
Firstpage :
307
Lastpage :
313
Abstract :
The authors outline the salient features of a protection technique for transmission lines which utilises the high frequency components of fault generated noise. The approach is based on the nonunit type scheme, which makes use of a stack-tuner circuit connected to the coupling capacitor of a capacitor voltage transformer. The stack-tuner is tuned to a certain frequency bandwidth and is arranged to act as a high frequency switch. The signals derived from the stack-tuner are used to determine whether the fault is inside or outside the protected zone
Keywords :
fault location; potential transformers; power transmission lines; protection; HF switches; capacitor voltage transformer; coupling capacitor; fault induced HF signal detection; power line protection; stack-tuner circuit;
fLanguage :
English
Journal_Title :
Generation, Transmission and Distribution, IEE Proceedings C
Publisher :
iet
ISSN :
0143-7046
Type :
jour
Filename :
103265
Link To Document :