DocumentCode
817679
Title
Improvements in RF monitoring system on generators
Author
Mohammed, Osama A. ; Mundulas, Jore
Author_Institution
Dept. of Electr. Eng., Florida Int. Univ., Miami, FL, USA
Volume
4
Issue
2
fYear
1989
fDate
6/1/1989 12:00:00 AM
Firstpage
237
Lastpage
243
Abstract
An improved RF monitoring system for generators is described. A capacitive coupling is shown to be much more sensitive than the currently used magnetic coupling through a current transformer. The increase in sensitivity results in an improved coupling between the generator´s neutral grounding lead and the monitor. An RC high-pass filter is shown to be an effective coupler, because it does not attenuate the RF noise or create saturation problems as in the case of magnetic coupling. By selecting an RC filter with higher capacitance than the stray capacitances created by the typical generator grounding transformer, the coupler can detect arcing signals in any generator, regardless of the type of neutral grounding transformer used. Even though there is an ohmic contact to the neutral lead, the protections to the added RF instrumentation assure that the protective relaying scheme is not degraded.<>
Keywords
electric generators; monitoring; RC high-pass filter; RF monitoring system; arcing signals; capacitive coupling; electric generators; grounding transformer; neutral grounding lead; Capacitance; Couplings; Current transformers; Filters; Grounding; Magnetic separation; Monitoring; Radio frequency; Saturation magnetization; Signal generators;
fLanguage
English
Journal_Title
Energy Conversion, IEEE Transactions on
Publisher
ieee
ISSN
0885-8969
Type
jour
DOI
10.1109/60.17917
Filename
17917