Abstract
Condition monitoring is playing an increasingly important role within electrical power networks, where its use can help to reduce maintenance costs, improve supply reliability, and permit increased utilization of equipment capacity by providing a measure of actual operating conditions as an alternative to relying on more stringent “worst case scenario” assumptions. In this context, energy harvesting may have a role to play in that it offers the possibility of realizing autonomous, self-powering sensors that communicate their data wirelessly. In the vicinity of electrical transmission and distribution equipment, alternating magnetic fields at the power frequency offer a potential source of energy that does not require hard-wiring or batteries. There are many potentially useful locations for sensors where the level of magnetic flux density may be sufficient to provide enough power for a low-power wireless sensor node. This paper describes a free-standing inductive harvester for use in positions where there is an ambient magnetic field due to conductors that are remote and/or inaccessible. Using data from surveys of magnetic flux density levels at two substations, optimum core and coil designs for the harvester are obtained through theoretical analyses and experiments. A demonstrator is then constructed in which a wireless sensor becomes self-powering when immersed in a 50-Hz magnetic field. Laboratory results show that this system can deliver a useful average power of 300 μW when placed in a magnetic flux density of 18 μTrms.
Keywords
condition monitoring; distribution networks; electric sensing devices; energy harvesting; magnetic field measurement; magnetic flux; magnetic sensors; power apparatus; substations; transmission networks; wireless sensor networks; alternating magnetic field; conductor; distribution equipment; electrical power network; electrical transmission; energy harvesting; equipment capacity utilization; free-standing inductive harvester; frequency 50 Hz; low-power wireless sensor node; magnetic flux density; maintenance cost reduction; optimum coil design; optimum core design; power 300 muW; power condition monitoring sensor; substation; supply reliability improvement; Coils; Magnetic cores; Magnetic fields; Magnetic sensors; Permeability; Substations; Condition monitoring; energy harvesting; inductive coupling; magnetic field; wireless sensors;
fLanguage
English
Journal_Title
Sensors Journal, IEEE
Publisher
ieee
ISSN
1530-437X
Type
jour
DOI
10.1109/JSEN.2013.2251625
Filename
6475142
Link To Document