DocumentCode :
822240
Title :
Implicitly constrained substation model for state estimation
Author :
De La Villa Jaén, Antonio ; Gómez-Expósito, Antonio
Author_Institution :
Dept. of Electr. Eng., Seville Univ., Spain
Volume :
17
Issue :
3
fYear :
2002
fDate :
8/1/2002 12:00:00 AM
Firstpage :
850
Lastpage :
856
Abstract :
This paper addresses the problem of including detailed substation models in state estimation at the least possible cost. After reviewing existing alternatives, it is shown how Lagrange multipliers associated with topological constraints can be easily computed from an implicit model the size of which is slightly larger than that of the conventional bus-branch approach. This allows bad data and topological error processing to be carried out simultaneously.
Keywords :
control system analysis; energy management systems; power system control; power system state estimation; substations; Lagrange multipliers; bad data processing; implicitly constrained substation model; power systems; state estimation; topological constraints; topological error processing; Circuit breakers; Computer errors; Costs; Load flow; Medical services; Redundancy; State estimation; Substations; Topology; Voltage;
fLanguage :
English
Journal_Title :
Power Systems, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8950
Type :
jour
DOI :
10.1109/TPWRS.2002.800979