Asymmetrical winding configuration to reduce inrush current with appropriate short-circuit current in transformer
Author
Chen, J.-F. ; Liang, T.-J. ; Cheng, C.-K. ; Chen, S.-D. ; Lin, R.-L. ; Yang, W.-H.
Author_Institution
Dept. of Electr. Eng., Nat. Cheng Kung Univ., Tainan, Taiwan
Volume
152
Issue
3
fYear
2005
fDate
5/6/2005 12:00:00 AM
Firstpage
605
Lastpage
611
Abstract
A method for transformer design with an asymmetric winding configuration to reduce the inrush current with appropriate voltage regulation and short-circuit current is proposed. Differing from the traditional symmetric winding structure in transformer design, this method can provide the high inrush equivalent inductance and suitable leakage inductance for a transformer. The formulas of the leakage inductance and inrush equivalent inductance are derived for the asymmetric winding configuration. Theoretical analyses showing the desirable winding configuration that the inrush current can be reduced to with appropriate voltage regulation and short-circuit current are presented. Using the inferential result in experiments, the inrush current can be successfully limited under a low voltage regulation and a suitable short-circuit current.
Keywords
short-circuit currents; transformer protection; transformer windings; voltage regulators; asymmetrical winding configuration; inrush current reduction; transformer design; transformer short-circuit current; voltage regulation;
fLanguage
English
Journal_Title
Electric Power Applications, IEE Proceedings -
Publisher
iet
ISSN
1350-2352
Type
jour
DOI
10.1049/ip-epa:20040985