• DocumentCode
    826300
  • Title

    A critical analysis of grounding practices for railroad tracks in electric utility stations

  • Author

    Garrett, D.L. ; Wallace, K.A.

  • Author_Institution
    Southern Co. Services, Birmingham, AL, USA
  • Volume
    8
  • Issue
    1
  • fYear
    1993
  • fDate
    1/1/1993 12:00:00 AM
  • Firstpage
    90
  • Lastpage
    96
  • Abstract
    This analysis looks for common trends of voltages along railroad tracks in a controlled model of a substation grounding system during a ground fault. Several cases are used to illustrate some of the most common techniques used to limit hazardous voltages, and some of these techniques are found to be quite ineffective. Except for cases in which the tracks near the substation were removed, the potential transferred along the tracks produced several scenarios which resulted in touch and/for step voltages exceeding the tolerable limits
  • Keywords
    earthing; railways; safety; substations; electric utility stations; grounding practices; hazardous voltages; railroad tracks; step voltages; substations; touch voltages; Foot; Fuels; Grounding; Insulation life; Power transformers; Rails; Roads; Soil; Substations; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.180323
  • Filename
    180323