• DocumentCode
    826320
  • Title

    Effects of deteriorated and contaminated substation surface covering layers on foot resistance calculations

  • Author

    Dawalibi, F.P. ; Xiong, W. ; Ma, J.

  • Author_Institution
    Safe Engineering Services & Technol. Ltd., Montreal, Que., Canada
  • Volume
    8
  • Issue
    1
  • fYear
    1993
  • fDate
    1/1/1993 12:00:00 AM
  • Firstpage
    104
  • Lastpage
    113
  • Abstract
    It is shown that significant inaccuracies can occur when the ANSI/IEEE Std 80 method for calculating foot resistances is applied in substations covered by a thin layer of crushed rock or similar covering layers. In particular, the errors obtained by using the infinite series expression of the foot resistance are consistently larger than those produced by the simplified expression for clean and contaminated surface layers
  • Keywords
    electric resistance; substations; ANSI/IEEE Std 80 method; contaminated surface layers; crushed rock; deteriorated surface layers; errors; foot resistance calculations; human foot; infinite series expression; substations; surface covering layers; ANSI standards; Electric resistance; Electric shock; Foot; Immune system; Stress; Substations; Surface contamination; Surface resistance; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.180325
  • Filename