DocumentCode :
826320
Title :
Effects of deteriorated and contaminated substation surface covering layers on foot resistance calculations
Author :
Dawalibi, F.P. ; Xiong, W. ; Ma, J.
Author_Institution :
Safe Engineering Services & Technol. Ltd., Montreal, Que., Canada
Volume :
8
Issue :
1
fYear :
1993
fDate :
1/1/1993 12:00:00 AM
Firstpage :
104
Lastpage :
113
Abstract :
It is shown that significant inaccuracies can occur when the ANSI/IEEE Std 80 method for calculating foot resistances is applied in substations covered by a thin layer of crushed rock or similar covering layers. In particular, the errors obtained by using the infinite series expression of the foot resistance are consistently larger than those produced by the simplified expression for clean and contaminated surface layers
Keywords :
electric resistance; substations; ANSI/IEEE Std 80 method; contaminated surface layers; crushed rock; deteriorated surface layers; errors; foot resistance calculations; human foot; infinite series expression; substations; surface covering layers; ANSI standards; Electric resistance; Electric shock; Foot; Immune system; Stress; Substations; Surface contamination; Surface resistance; Voltage;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/61.180325
Filename :
180325
Link To Document :
بازگشت