• DocumentCode
    826330
  • Title

    Verification of the seismic resistance of gas-insulated switchgear (GIS)

  • Author

    Buck, K.E. ; Kleine-Tebbe, A. ; Rees, V.

  • Author_Institution
    ABB Corp. Res., Heidelberg, Germany
  • Volume
    8
  • Issue
    1
  • fYear
    1993
  • fDate
    1/1/1993 12:00:00 AM
  • Firstpage
    114
  • Lastpage
    120
  • Abstract
    A brief introduction to the background of seismic requirements is given, and the test procedure for demonstrating the capability of gas-insulated switchgear (GIS) to withstand seismic stresses up to highest ground accelerations of 0.75 g. are described. The verification methods for checking the test object after test are also described. As vibrational tests are very cost-intensive and therefore can only be performed with a representative switchgear arrangement, a calculation method for demonstrating the seismic withstand behavior of practical switchgear arrangements is presented. The tests and calculation results demonstrate the suitability of a three-pole common enclosed GIS design for 145/170 kV for horizontal ground accelerations up to 0.75 g
  • Keywords
    gaseous insulation; switchgear; test facilities; 145 kV; 170 kV; 3-pole common enclosed GIS; gas-insulated switchgear; ground accelerations; seismic resistance; testing; Earthquakes; Gas insulation; Geographic Information Systems; Gravity; Life estimation; Performance evaluation; Stress; Substations; Switchgear; Testing;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.180326
  • Filename
    180326