    Development of improved methods for type testing present day medium voltage circuit breakers for outdoor service

  • Author

    Kuznetsov, Stephen B. ; Spindle, Harvey E.

  • Author_Institution
    PSM High Power Labs., East Pittsburgh, PA, USA
  • Volume
    8
  • Issue
    1
  • fYear
    1993
  • fDate
    1/1/1993 12:00:00 AM
  • Firstpage
    193
  • Lastpage
    196
  • Abstract
    Type testing for fault currents for medium-voltage circuit breakers rated at 15 kV to 72.5 kV is addressed. The ANSI designation of a new class of definite-purpose circuit breakers capable of switching transformer secondary faults and the introduction of the requirement for short-line-fault tests for breakers rated 72.5 kV and below have increased the difficulty of performing type tests in a testing laboratory. It is concluded that synthetic testing using the parallel current injection circuit is described in ANSI C37.081 provides the best available method for proving these complex requirements for medium-voltage circuit breakers
  • Keywords
    circuit breakers; testing; 15 to 72.5 kV; ANSI C37.081; MV circuit breakers; fault currents; short-line-fault tests; transformer secondary faults; type testing; Circuit breakers; Circuit faults; Circuit testing; Frequency; Inductors; Laboratories; Medium voltage; Petroleum; Transformers; Transient analysis;