DocumentCode
826604
Title
Accelerated aging and flashover tests on 138 kV nonceramic line post insulators
Author
Schneider, H.M. ; Guidi, W.W. ; Burnham, J.T. ; Gorur, R.S. ; Hall, J.F.
Author_Institution
EPRI High Voltage Transmission Res. Center, Lenox, MA, USA
Volume
8
Issue
1
fYear
1993
fDate
1/1/1993 12:00:00 AM
Firstpage
325
Lastpage
336
Abstract
The behavior of 138 kV nonceramic line post insulators is investigated by means of clean fog tests conducted before and after aging in a specially designed accelerated aging chamber. The laboratory aging cycles are justified on the basis of actual weather in the coastal regions of Florida. Analytical measurements quantifying the degree of artificial aging are discussed, and artificial aging is compared with service experience. Observations of audible noise and radio influence voltage during the clean fog tests are reported
Keywords
ageing; flashover; insulators; testing; 138 kV; Florida; accelerated ageing; artificial aging; audible noise; clean fog tests; coastal regions; flashover tests; line post insulators; radio influence voltage; Accelerated aging; Acoustic noise; Contamination; Flashover; Insulation; Insulator testing; Laboratories; Lightning; Senior members; Voltage;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/61.180353