• DocumentCode
    826700
  • Title

    Arc furnace flicker measurements and control

  • Author

    Bhargava, Bharat

  • Author_Institution
    Southern California Edison Co., Rosemead, CA, USA
  • Volume
    8
  • Issue
    1
  • fYear
    1993
  • fDate
    1/1/1993 12:00:00 AM
  • Firstpage
    400
  • Lastpage
    410
  • Abstract
    The results of arc flicker investigations and harmonic measurements taken on a 55 MW arc furnace are presented. The arc furnace has been in operation since 1976 and has a 65 MVAr static VAr system (SVS) installed to improve the customer´s power factor, reduce the voltage fluctuations. and arc furnace flicker. Although the SVS improved the power factor and reduced the voltage fluctuations and incandescent lamp flicker, it caused considerable fluorescent flicker, which was specially noticeable at some remote locations about ten miles away
  • Keywords
    arc furnaces; harmonics; random noise; static VAr compensators; 55 MW; 65 MVAr; SVS; arc flicker; arc furnace; fluorescent flicker; harmonic measurements; incandescent lamp flicker; power factor; static VAr system; voltage fluctuations; Circuits; Fluorescence; Furnaces; Gain measurement; Manufacturing; Power measurement; Reactive power; Steel; Transmission line measurements; Voltage fluctuations;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.180362
  • Filename