DocumentCode
827906
Title
Power flow in four-wire distribution networks-general approach
Author
Ciric, Rade M. ; Feltrin, Antonio Padilha ; Ochoa, Luis F.
Author_Institution
Univ. Estadual Paulista, Ilha Solteira, Brazil
Volume
18
Issue
4
fYear
2003
Firstpage
1283
Lastpage
1290
Abstract
The neutral wire in most power flow software is usually merged into phase wires using Kron´s reduction. Since the neutral wire and the ground are not explicitly represented, neutral wire and ground currents and voltages remain unknown. In some applications, like power quality and safety analyses, loss analysis, etc., knowing the neutral wire and ground currents and voltages could be of special interest. In this paper, a general power flow algorithm for three-phase four-wire radial distribution networks, considering neutral grounding, based on backward-forward technique, is proposed. In this novel use of the technique, both the neutral wire and ground are explicitly represented. A problem of three-phase distribution system with earth return, as a special case of a four-wire network, is also elucidated. Results obtained from several case studies using medium- and low-voltage test feeders with unbalanced load, are presented and discussed.
Keywords
distribution networks; earthing; load flow; Kron´s reduction; backward-forward technique; earth return; four-wire distribution networks; four-wire network; ground currents; low-voltage test feeders; medium-voltage test feeders; neutral grounding; neutral wire currents; phase wires; power flow; power flow software; three-phase distribution system; three-phase four-wire radial distribution networks; unbalanced load; Application software; Earth; Grounding; Intelligent networks; Load flow; Medium voltage; Power quality; Robustness; Safety; Wire;
fLanguage
English
Journal_Title
Power Systems, IEEE Transactions on
Publisher
ieee
ISSN
0885-8950
Type
jour
DOI
10.1109/TPWRS.2003.818597
Filename
1245548