DocumentCode
829131
Title
New method for measurement of the resistive leakage currents of metal-oxide surge arresters in service
Author
Lundquist, J. ; Stenström, L. ; Schei, A. ; Hansen, B.
Author_Institution
Asea Brown Boveri HV Switchgear, Ludvika, Sweden
Volume
5
Issue
4
fYear
1990
fDate
10/1/1990 12:00:00 AM
Firstpage
1811
Lastpage
1822
Abstract
Various methods of determining the condition of zinc oxide (ZnO) surge arresters by means of measuring their leakage current are discussed. A method that minimizes the influence of harmonics in the system voltage when performing a harmonic analysis of the arrester leakage current presented. The presence of harmonics in the voltage has presented a great problem to earlier methods based on harmonic analysis, since these harmonics may interfere with the harmonics generated by the nonlinear resistance of the arrester. The favorable effect of the method presented is achieved by introducing a field probe which allows a compensation for the harmonics in the voltage. The main advantage of the new method is the low sensitivity to harmonics in the system voltage
Keywords
electric current measurement; harmonic analysis; surge protection; zinc compounds; ZnO surge arresters; field probe; harmonic analysis; leakage current measurement; nonlinear resistance; resistive leakage currents; Arresters; Capacitance; Current measurement; Harmonic analysis; Leakage current; Power system harmonics; Surge protection; Varistors; Voltage; Zinc oxide;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/61.103677
Filename
103677
Link To Document