DocumentCode :
829455
Title :
Estimation of fast transient overvoltage in gas-insulated substation
Author :
Yanabu, S. ; Murase, H. ; Aoyagi, H. ; Okubo, H. ; Kawaguchi, Y.
Author_Institution :
Toshiba Corp., Kawasaki, Japan
Volume :
5
Issue :
4
fYear :
1990
fDate :
10/1/1990 12:00:00 AM
Firstpage :
1875
Lastpage :
1882
Abstract :
The authors measured FTO (fast transient overvoltages) at various points of a commercial 550 kV gas-insulated substation (GIS) by operating energized disconnectors. Based on the results of these measurements, the possible levels of FTO at various points of the GIS and the probability of occurrence of large levels are discussed. Laboratory tests were also performed by using a recently developed 1 GHz surge sensor to check on the insignificance of high-frequency components due to short-surge impedance discontinuities such as spacers, disconnectors, and short bus branches. Waveforms calculated by rough simulation that ignored the short surge impedance discontinuities are compared with measured waveforms at the commercial substation, proving that simulated FTO levels agreed well with measured values
Keywords :
gaseous insulation; overvoltage; substations; transients; 1 GHz; 550 kV; disconnectors; fast transient overvoltage; gas-insulated substation; short bus branches; short-surge impedance discontinuities; spacers; surge sensor; Bars; Circuit simulation; EMTP; Gas insulation; Geographic Information Systems; Impedance; Substations; Surges; Switchgear; Voltage control;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/61.103684
Filename :
103684
Link To Document :