Relationship between partial discharge pulse height analysis and subsequent voltage endurance of stator bars and coils
Author
McDermid, W. ; Bromley, J.C.
Author_Institution
Manitoba Hydro, Winnipeg, Man., Canada
Volume
7
Issue
4
fYear
1992
fDate
12/1/1992 12:00:00 AM
Firstpage
721
Lastpage
731
Abstract
A method has been developed for screening stator bars and coils using a particular type of partial discharge (PD) detector. The objective in making PD screening tests was to identify those bars or coils which are more likely to fail on voltage endurance in a relatively short time. The majority of the examples given pertain to a project involving ten hydroelectric generators which had a total of 10800 stator bars. Evidence is presented which suggests that the test method is more sensitive to internal discharges than to those associated with the end grading surfaces
Keywords
failure analysis; hydroelectric generators; machine testing; partial discharges; reliability; stators; between partial discharge pulse height analysis; failure analysis; hydroelectric generators; internal discharges; machine testing; project; reliability; screening tests; stator bars; stator coils; voltage endurance; Circuit testing; Coils; Instruments; Insulation; Partial discharges; Pulse measurements; Stator bars; Stator windings; Stress; Voltage;