DocumentCode :
829745
Title :
Fourteen Years of Data on the Operation of One Hundred Ungrounded 240-and 480-Volt Industrial Distribution Systems
Author :
Gienger, John A.
Author_Institution :
Eastman Kodak Company
Issue :
2
fYear :
1966
fDate :
3/1/1966 12:00:00 AM
Firstpage :
147
Lastpage :
150
Abstract :
A discussion is given of the data found over a fourteen-year period of 240-and 480-volt ungrounded industrial distribution system operation at Kodak Park Works, Eastman Kodak Company. An advantage of the ungrounded system over the grounded system is the higher degree of reliability that is attainable. One drawback of the system is the problem of locating a ground when it occurs. Practical and successful tracing of grounds with power on are possible and, when combined with systematic detecting and clearing, the ungrounded system may offer further advantages over the grounded system.
Keywords :
Chemical industry; Chemical processes; Circuits; Coils; Conductors; Industrial accidents; Industrial power systems; Manufacturing industries; Manufacturing processes; Power system reliability;
fLanguage :
English
Journal_Title :
Industry and General Applications, IEEE Transactions on
Publisher :
ieee
ISSN :
0018-943X
Type :
jour
DOI :
10.1109/TIGA.1966.4180636
Filename :
4180636
Link To Document :
بازگشت