DocumentCode :
830513
Title :
Performance of the Pramod Johns scheme for UHS protection of EHV transmission lines under arcing fault conditions
Author :
Agrawal, Pramod
Author_Institution :
Power Syst. Consultants, London, UK
Volume :
6
Issue :
1
fYear :
1991
fDate :
1/1/1991 12:00:00 AM
Firstpage :
127
Lastpage :
134
Abstract :
The performance of the scheme of Pramod Agrawal (1989) for ultra-high-speed (UHS) protection of EHV transmission lines under arcing fault conditions is described. The arc with reignition effect is modeled, and a method for digital simulation of the superimposed arc voltage is discussed. Simulated tests have shown that the arc voltage has significant higher-frequency components. These tests also confirm that the arcing fault response repeats every half-cycle for a fault inception angle of the voltage from 0 to 90°, which is a significant improvement over schemes based on traveling-wave phenomena which have been considered a failure for faults at 0°C fault inception
Keywords :
arcs (electric); electrical faults; protection; transmission lines; EHV transmission lines; Pramod Johns scheme; UHS protection; arc voltage; arcing fault conditions; digital simulation; fault inception angle; reignition effect; ultra-high-speed protection; Circuit faults; Frequency; Power system protection; Power system transients; Power transmission lines; Switches; Transmission lines; Tuned circuits; Tuners; Voltage;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/61.103731
Filename :
103731
Link To Document :