• DocumentCode
    830712
  • Title

    Distribution system harmonic design

  • Author

    Ortmeyer, Thomas H. ; Zehar, Khaled

  • Author_Institution
    Dept. of Electr. & Comput. Eng., Clarkson Univ., Potsdam, NY, USA
  • Volume
    6
  • Issue
    1
  • fYear
    1991
  • fDate
    1/1/1991 12:00:00 AM
  • Firstpage
    289
  • Lastpage
    294
  • Abstract
    A new method is described for distribution system harmonic design. It is based on the application of the eigenvalue sensitivity technique to the system poles and zeros. The harmonic voltage performance of a distribution system depends on the location of its poles and zeros with respect to the harmonic frequencies. The knowledge of the poles, the zeros and their respective sensitivities to system parameters enables the designer to identify changes in the system which will reduce harmonic voltage levels. These system changes are readily apparent using the proposed method, resulting in less computational effort and reduced engineering time. This approach often results in small changes in the capacitor bank locations, in which case the 60 Hz performance is not substantially changed
  • Keywords
    distribution networks; eigenvalues and eigenfunctions; harmonics; poles and zeros; power capacitors; power system CAD; sensitivity analysis; 60 Hz; capacitor bank; distribution system; eigenvalue sensitivity technique; harmonic; poles and zeros; power system CAD; Capacitors; Eigenvalues and eigenfunctions; Impedance; Laplace equations; Power engineering and energy; Power engineering computing; Power system harmonics; Resonant frequency; Student members; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.103750
  • Filename