DocumentCode :
834645
Title :
Unsynchronised two-terminal transmission-line fault-location without using line parameters
Author :
Liao, Y. ; Elangovan, S.
Author_Institution :
Dept. of Electr. & Comput. Eng., Univ. of Kentucky, KY
Volume :
153
Issue :
6
fYear :
2006
fDate :
11/1/2006 12:00:00 AM
Firstpage :
639
Lastpage :
643
Abstract :
The paper presents a new two-terminal transmission-line fault-location algorithm without requiring line parameters. The voltage and current measurements at both ends of a transmission line during a fault are assumed to be available and no synchronisation of the data is required. The proposed algorithm is suitable for estimating the location of asymmetric faults on a line when line parameters are not available. Evaluation studies using both simulated and field data are reported
Keywords :
electric current measurement; fault location; power system simulation; power transmission faults; power transmission lines; voltage measurement; current measurement; data synchronisation; fault-location; two-terminal transmission-line; voltage measurement;
fLanguage :
English
Journal_Title :
Generation, Transmission and Distribution, IEE Proceedings-
Publisher :
iet
ISSN :
1350-2360
Type :
jour
DOI :
10.1049/ip-gtd:20060026
Filename :
4015886
Link To Document :
بازگشت